Dual Display NPN, PNP, TTL, Namur, Tacho or Closed Contact, 2×6-digit Panel Meter/Controller

Additional information

Weight 0.869 kg
Dimensions 11.8 × 16.9 × 5.9 cm
Power Supply

– 85-265V AC / 95-370V DC (HV)
– 15-48V AC / 10-72V DC (LV)

Relay Output

– None
– 2x Relay Outputs
– 4x Relay Outputs

Analog Output

– None
– 1x 4-20mA / 0-10V

Serial Port

– None
– 1x RS232 (RJ Terminal)
– 1x RS485 (Screw Terminal)

Share This Product

What it does

Accepts digital pulse inputs from flow sensors and meters. Dual display shows the flow rate and volume.

This dual display flow batching totalizer accepts a variety of flow sensor inputs, and has a variety of advanced features, including: flow batching, volumetric pulse, in flight adjustment, setpoint latching, startup inhibit and user programmable input functions.

At a glance:

  • NPN, PNP, TTL, namur, tacho or closed contact sensors
  • Single totalizer
  • Customisable display source, front panel button and rear input pins
  • Batching feature
  • Advanced setpoint features, including setpoint trailing, volumetric pulse, latching, startup inhibit and inflight adjustment
  • Calibrate using direct K factor entry or pulses/unit method
  • Signal averaging on the rate
  • Dual display for simultaneous viewing of total and rate

Specifications

Input


Sensor input: NPN, PNP, TTL, namur, tacho or closed contact


Excitation: 24V DC (50mA max)


Accuracy: 0.005%


Ambient drift: Typically 2ppm/°C


K Factor ranges: 0.1 to 99.9999, 999.999 or 9999.99


Noise filtering: 0.2, 2, 20kHz or Off


Input frequency: 2Hz to 10kHz


Calibration: Direct K factor entry or pulses per unit of measurement


Power


Power supply: High voltage 85–265V AC / 95–370V DC, or Low voltage 15–48V AC / 10–72V DC


Relay Output


Number of relay outputs: None, 2 or 4


Relay output type: 5A form A (3A 240V AC max or 3A 30V DC max)


Analog Output (Retransmission)


Number of analog outputs: None or 1


Analog output type: Isolated 16 bit 4–20mA/0–10V


Features: Window programmable over any range within the full scale range of the controller


Comm Port(s)


Number of comm ports: None or 1


Serial port configuration: Isolated RS232 (screw terminal) or RS485 (RJ11 terminal)


Output mode: Define ASCII, Modbus RTU slave or Ranger A


Baud rates: 1200-115k2 baud


Parity: Odd, even, or none


Programming


Front panel buttons: Up, Down, P (Prog/Enter), plus 2x Function Buttons for menu access


Display


Display type: LED display, 5 buttons


LED indicators: 6 setpoint indicator LEDs


Digits: 2 rows of 6 digits, 0.4″ (10mm), 14 segment alphanumeric LED


Construction


Casing: Panel mount case


Ingress protection rating: IP65 dust/splash proof (face only)


Dimensions (H x W x D): 1.9 x 3.8 x 4.7″ (48 x 96 x 120mm)


Cutout area: 1.79 x 3.64″ (45.5 x 92.5mm)


Documents

PRO-FLO200 Manual 19V01, 06-Mar-2019 | (9972 KB)

Order Codes

PRO-FLO200

-HV 85-265V AC / 95-370V DC
-LV 15-48V AC / 10-72V DC
Relay Output
  None
-R2 2 x relay outputs
-R4 4 x relay outputs
Analog Output
  None
-A 1 x 4-20mA/0-10V analog output
Comms
  None
-S2R 1 x RS232 serial port (RJ11 terminal)
-S4S 1 x RS485 serial port (screw terminal)
Sample order codes: PRO-FLO200-HV, PRO-FLO200-HV-A-S2R, PRO-FLO200-HV-R2, PRO-FLO200-HV-R2-A, PRO-FLO200-HV-R2-A-S2R, PRO-FLO200-HV-R2-S2R, PRO-FLO200-HV-R4, PRO-FLO200-HV-R4-A, PRO-FLO200-HV-R4-A-S2R, PRO-FLO200-HV-R4-S2R, PRO-FLO200-HV-S2R, PRO-FLO200-LV, PRO-FLO200-LV-A-S2R, PRO-FLO200-LV-R2, PRO-FLO200-LV-R2-A, PRO-FLO200-LV-R2-A-S2R, PRO-FLO200-LV-R2-S2R, PRO-FLO200-LV-R4, PRO-FLO200-LV-R4-A, PRO-FLO200-LV-R4-A-S2R, PRO-FLO200-LV-R4-S2R, PRO-FLO200-LV-S2R, PRO-FLO200-R2-HV, PRO-FLO200-R4-HV, PRO-FLO200-R2-LV, PRO-FLO200-R4-LV